J1V3 Reference Building - Control Thermostat

Many of us know J1V3 modelling requirements. Specification 34 sets them out for the reference and proposed buildings in a clear and relatively concise manner.

One of the lesser-known components of J1V3 modelling is the requirement to determine specific air conditioning setpoints for 98% of the annual hours of operation, when the occupancy of the building is greater than 20% of the peak occupancy.

More detail can be found in S34C2 Reference building (c)

For conditioned spaces with transitory occupancy, the reference building must maintain between 18ยฐCDB and 25ยฐCDB, while all other conditioned spaces should have temperatures maintained between 21ยฐCDB and 24ยฐCDB. This of course means that your reference and proposed building can differ.

Additionally, if the proposed building either lacks mechanical cooling or employs mixed mode cooling, the air-conditioning system must use the same method of control and set points for non-mechanical cooling as specified for the proposed building.

Reference Building Control Settings on Speckel

When viewing a J1V3 workflow, a Reference tab is visible on the left side of the screen. Here, you will find the Control Thermostat. When active, the reference building zones use either a thermostat of 21 - 24 CDB (when a 'Conditioned Space'), or 18 - 25 CDB (when a 'Transitory Space'). This setting can be controlled for each Space.

Last updated