J1V3 Verification using a reference building

(1) For a Class 3, 5, 6, 7, 8 or 9 building or common area of a Class 2 building, compliance with J1P1 is verified whenβ€”

  1. it is determined that the annual greenhouse gas emissions of the proposed building are not more than the annual greenhouse gas emissions of a reference building whenβ€”

    1. the proposed building is modelled with the proposed services; and

    2. the proposed building is modelled with the same services as the reference building; and

  2. in the proposed building, a thermal comfort level of between a Predicted Mean Vote of -1 to +1 is achieved across not less than 95% of the floor area of all occupied zones for not less than 98% of the annual hours of operation of the building; and

  3. the building complies with the additional requirements in Specification 33.

(2) The annual greenhouse gas emissions of the proposed building may be offset byβ€”

  1. renewable energy generated and used on site; and

  2. another process such as reclaimed energy, used on site.

(3) The calculation method used for (1) and (2) must comply withβ€”

  1. ANSI/ASHRAE Standard 140; and

  2. Specification 34.