JV3 Verification using a reference building

JV3 has been reproduced without amendment, as per NCC 2019 - Vol 1 - Amendment 1.

(a) For a Class 3, 5, 6, 7, 8 or 9 building or common area of a Class 2 building, compliance with JP1 is verified whenβ€”

(i) it is determined that the annual greenhouse gas emissions of the proposed building are not more than the annual greenhouse gas emissions of a reference building whenβ€”

(A) the proposed building is modelled with the proposed services; and

(B) the proposed building is modelled with the same services as the reference building; and

(ii) in the proposed building, a thermal comfort level of between a Predicted Mean Vote of -1 to +1 is achieved across not less than 95% of the floor area of all occupied zones for not less than 98% of the annual hours of operation of the building; and

(iii) the building complies with the additional requirements in Specification JVa.

(b) The annual greenhouse gas emissions of the proposed building may be offset byβ€”

(i) renewable energy generated and used on site; and

(ii) another process such as reclaimed energy, used on site.

(c) The calculation method used for (a) and (b) must comply withβ€”

(i) ANSI/ASHRAE Standard 140; and

(ii) Specification JVb.