H1/AS1 Schedule Method
H1/AS1 Schedule Method has been reproduced without amendment, as per H1/AS1 Fifth Edition Amendment 1.
2.1.2.1 The Schedule Method shall only be used where:
a) The glazing area is 30% or less of the total wall area; and
b) The combined glazing area on the east, south, and west-facing walls (refer to Appendix D) is 30% or less of the combined total area of these walls; and
c) The skylight area is no more than 1.5 m2 or 1.5% of the total roof area (whichever is greater);
d) The opaque door area is no more than 6 m2 or 6% of the total wall area (whichever is greater).
2.1.2.2 Building elements that are part of the thermal envelope shall have minimum construction R-values no less than those in:
a) For building elements that contain embedded heating systems, those in Table 2.1.2.2A; or
b) For building elements that do not contain embedded heating systems, those in Table 2.1.2.2B. i) Table 2.1.2.2B or
ii) alternatively, for housing only, for building consent applications submitted before 1 May 2023, those in Table 2.1.2.2C. 2.1.2.3 For building consent applications submitted before 2 November 2023, the minimum construction R-values for windows and doors in climate zones 1 and 2 are permitted to be reduced to R0.37 m²·K/W.
Table 2.1.2.2A: Minimum construction R-values for heated ceilings, walls or floors
Building element | Climate zone 1 | Climate zone 2 | Climate zone 3 | Climate zone 4 | Climate zone 5 | Climate zone 6 |
---|---|---|---|---|---|---|
Heated ceiling | R6.6 | R6.6 | R6.6 | R6.6 | R6.6 | R6.6 |
Heated wall | R2.9 | R2.9 | R2.9 | R2.9 | R2.9 | R2.9 |
Heated floor | R2.5 | R2.5 | R2.5 | R2.8 | R3.0 | R3.0 |
Table 2.1.2.2B: Minimum construction R-values for building elements that do not contain embedded heating systems
Building element | Climate zone 1 | Climate zone 2 | Climate zone 3 | Climate zone 4 | Climate zone 5 | Climate zone 6 |
---|---|---|---|---|---|---|
Roof | R6.6 | R6.6 | R6.6 | R6.6 | R6.6 | R6.6 |
Wall | R2.0 | R2.0 | R2.0 | R2.0 | R2.0 | R2.0 |
Floor Slab-on-ground floors | R1.5 | R1.5 | R1.5 | R1.5 | R1.6 | R1.7 |
Floors other than slab-on-ground | R2.5 | R2.5 | R2.5 | R2.8 | R3.0 | R3.0 |
Windows and doors | R0.46(3) | R0.46(3) | R0.46 | R0.46 | R0.50 | R0.50 |
Skylights | R0.46 | R0.46 | R0.54 | R0.54 | R0.62 | R0.62 |
Table 2.1.2.2C: Alternative minimum construction R-values for building elements that do not contain embedded heating systems - for housing only where building consent applications are submitted before 1 May 2023.
Building element | Region A | Region B |
---|---|---|
Roof | R2.9 | R3.3 |
Wall | R1.9 | R2.0 |
Floor | R1.3 | R1.3 |
Windows and doors | R0.37 | R0.37 |
Skylights | R0.37 | R0.37 |